Hubbell Industrial Controls LX908 Remote Fire Pump Alarm Panel November 1997 Instruction Manual Hubbell Industrial Controls Inc 50 Edwards St Madison Ohio 44057 Telephone 440 428 1161 Fax 440 428 7635 Model LX908 Remote Alarm Panel The purpose of the alarm panel is to monitor up to eight remote normally closed contacts and give both an audible and visual alarm if one or more of the remote contacts open The remote alarm contact must be a dry contact or damage to the main board will occur When the first remote contact opens indicating an alarm condition the alarm hom will sound and the respective alarm light will come on The hom can be silenced by pressing the silence pushbutton The alarm light will remain lit until the alarm condition is ...